Introduction of the Strukchture Workshop

User Rating: 5 / 5

Star ActiveStar ActiveStar ActiveStar ActiveStar Active
 

Requirements for the construction and design of the body of power boards:

 

All boards, including wall and stand, low pressure, distribution and steering will be made from a grainy (1.5-2.5) mm thick oil sheet.

The skeleton of low pressure stand boards is made of 2 mm steel and oiled sheets.

The body of the boards is made up of two chassis and body (cover), which are connected by a bolt and bolt.

Multi-cellular panels are made up of separate cells that bind together bolts and nuts.

It is possible to construct a door with lock and hinges and a screw and nut in four directions for the signs.

Cells are constructed in such a way that they have enough space and that the inspection and repairs and the access to the equipment and the shingles are easily carried out and, at the same time, can be developed at any time.

In order to prevent possible damage, the installation of main equipment for control, measurement and location of cable entry and exit is done separately. Measuring equipment will be installed in the front of the cell and at the top of it, so that it can be easily seen and used.

The body of the panels is constructed in such a way that any changes in the signs are possible without the need for welding and painting. (Prediction of proper holes and displacement with bolts and nuts)

In the upper part of the board, it is anticipated that the hooks are suitable for carrying the signs.

In the signs, a cable gland or cable gland is planned for input and output cables.

The degree of protection (IP) defined by the international protection system determines the level of electronic sealing in accordance with IEC 592 and IEC 60.529. Depending on the type of use of the signs and at the request of the employer, the degree of protection of the panel is determined and up to Protection degree IP68 is applicable

In the section of the lid, a local panel is considered for placing the drawings

In the structure of the strucker, the panels are made in two common types (weld, hinge, rectangular, nut, nut and nut) and Rital using advanced machines.

According to the designed maps and the type of selected cell of the metalwork operation, if the selected cell is of a standard type, only the standard parts that are already produced are collected and further operations performed on them, and if the non-standard parts in It will be done using the design and assistance from the machines of this unit, cutting operations, drilling, bending and welding operations are done on them.

The assembly of welding and joints is carried out by welding and following the necessary checks on the quality of the operations and the rotation of the welded parts of the parts

The cell monocyte is firstly assembled and then disassembled and transferred to the color line.

 

 

The items in the stricks of the low pressure wall panels of the rhythm type, or the half-bolt and the type of mold. Type or model: Wall-mounted - Raincoat, manufactured by Fajr Pavlovo Industries:

 

The sheet used is of oily type with a thickness of 1.5-1.25 mm and standard in the direction of the binder, but not the roll, due to the lack of a wave in the stacker panel.

The floor and the ceiling are separated by a panel. In accordance with the layout plan for entering and leaving the cables, the fiber should be separated from the body by a screw or screwdriver.

Welding operations are performed to prevent the boiling waste from CO2 boiling

In the case of preventing the entry of dust in the body of the panel without a hole, and the seat of the door on the body is made in the form U

Use the M6-M8 bolt to fasten the door and body to the inside of the lower hinged side panel.

The stroke of the panel is completely geometric, or the three sides of the upper and outer faces are equal and free of differences or running.

All protective covers, with the standard distance, are to be anticipated and, under no circumstances, should be used with bolts and nuts to open the butterfly nuts. Covers are made in a manner that covers all equipment and terminals.

In the rainbow boards, the cap can be divided into the ceiling of the bolt and the panel and can be detached from the inside of the panel and under no circumstances will the ceiling of the panel be boiled or disconnected.

Door boards larger than 60-50 centimeters to create more durability and more mechanical strength, be sure to roll and tin

On the wall boards, install the panels to the wall

All bolts and sticks used Type 8 × 8 All hinges and locks are a good and stainless steel model.

The internal board is made of galvanized sheet with a thickness of 1.5 mm and a circle (corners)

The board is equipped with a pocket or a map

Welding surfaces should be completely clean and do not use any conditions before or after paint

If the height of the panel exceeds 130-120 in the boards and the height of the board, the hook hook (not approved) can be predicted on the ceiling.

The stacker should be designed and constructed in such a way that it can not be watched under any conditions after color (no corrosion or rust)

The stacker of the panel should be designed and constructed, if necessary, equipped with air inlet and outlet air filter valves. Criteria for the layout of the panel

Items that are in the stroke of low pressure boards. Type: Rittal - All bolts and nuts - Half bolts and nuts - Fused, Fajr industries are manufactured:

 

Oiled and galvanized sheet with thickness of 2.5-2.5 mm and standard type in the direction of binder and not roll, due to the absence of wave in the stacker. STEEL GRADE: RRST13 DIN1623

The floor of the panel or roof, in accordance with the layout plan for entering and leaving the cables, has the function of removing the body from the body by means of a screw or screwdriver. Layout map layout

In the half bolts and nuts and wicker boards. Welding operations are to be performed to prevent weld waste by using CO2 welding

In the Rittal bridges and all bolts and nuts, bolts and nuts and mats, to prevent the entry of dust in the body of the panel without a hole, and the floor space on the door on the body is to be sealed and sealed with a suitable yalash foam.

Door and body doors from the inside of the lower hinge panel to use the M6-M8 bolt.

The stroke of the panel is completely geometric, or the three sides of the upper and outer faces are equal and free of differences or running.

All protective covers, with the standard distance, are to be anticipated and no bolts and nuts should be used in any way. To open the butterfly bolt, the panel holder should be hinged on request and the cover is equipped with a screwdriver screw (Winding screw). The covers are implemented in a manner that covers all equipment and terminals

In the rainbow boards, the warhead is placed on the ceiling of the bolt and nut panel and can be detached from the inside of the panel and under no circumstances shall be separated from the ceiling of the panel.

Door panels due to mechanical durability of steel and cans

All bolts and slicks used are galvanized Type 8 × 8 All hinges and locks are a good and stainless steel model.

In the Rittal bridges and all bolts, all of the equipment is structured in a way (separated) in a way that according to the need to develop the lateral and upper side of the design.

The stacker should be designed and constructed in such a way that it can not be watched under any conditions after color (no corrosion or rust)

Each cell is equipped with four hooks of bolt and thread made of steel. Swing revolving is not approved.

The stroke of the panel should be designed and constructed, if necessary, equipped with an air inlet and outlet air filter. Values ??Map layout

 

Items that are executed in a vertical crossover of an average compressor board and an open 24 kV produced in an organization:

 

Oiled and galvanized sheets with a thickness of 2.5-2.5 mm are of standard type in the binder and not in rolls, due to the absence of a wave in the stacker panel.

The floor of the panel, in accordance with the layout plan for entering and leaving the cables, is capable of being detached from the body by means of a screw or screwdriver. The symmetry or center of the cable entry point and the cable holder and the cable connection to the connection point is required. If the center is not obeyed, the probability and destruction of the cable head due to the curvature There is

In the relevant boards. Welding operations to prevent welding by welding (three to two)

In the relevant boards, prevent the entry of dust in the body of the hollow panel

All doors are connected to the inside of the panel for using the bolt (M8 and M6).

The stroke of the panel is completely geometric, or the three sides of the upper and outer faces are equal and free of differences or running.

In the bus compartment many times, the input and output chamber, and the current and voltage transitions of the explosion valve are required.

All doors that are connected to medium pressure equipment have the ability to open the racks when the sensor, de-genset and transmissions are flowing and pulsed, except for the control and protection door and the low pressure measurement. Mechanical or electrical interlock for all doors

The connection of the intermediate pressure cell to the low pressure (winding) of the area is carried out or predicted not to occur in the basin or the field (minimum distance 20 kV 21 cm), low pressure cabin or control, protection under no circumstances associated with the medium pressure cabin Wingering is out of bounds by Gland)

All bolts used for galvanizing and all hinges and locks will be of a good quality (8 to 8) and stainless steel

In the relevant boards, the structure of the panel should be in a way that according to the need to develop the development of the side view

The stacker should be designed and constructed in such a way that it can not be watched under any conditions after color (no corrosion or rust

Each cell is equipped with four hooks of bolts and nuts made of steel. Rotational swing is not approved.

In low pressure cabinets or controls, the entrance of the control cable (Transmission Control - Bucher Hutts) in the cockpit outside the basin or field is foreseeable.

Contact Us

Head office: Unit 15, No. 10, Seyyed Jamaloddin Asad Abadi Ave. 54, Tehran, Iran

Phone: +98 21 88052908-9

Fax: +98 21 88034297

Factory: Shayegan St., Amirkabir Blvd., Industrial Town No. 1, Arak, Iran

Phone: +98 86 34130501-3

Work from the Research and Development Unit of Fajr Central Bank. Copyright is reserved.

Search